The TRADELINE intermittent ignition oil primary control operates the oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat from the thermostat. Through a C554 Cad Cell Flame Sensor, the R8184 monitors the burner flame and shuts down the system on ignition failure or on flame failure during the run cycle. A light emitting diode (LED) on the terminal strip lights when the safety switch opens to provide safety shutdown indication. A manual reset button is provided to reset the safety switch after lockout. For convenience in system maintenance, the safety switch can be manually opened using a lever on the front of the control. Clock thermostats that power the clock through the primary control transformer will lose time during lockout unless backup batteries are installed.
Operates the oil burner and oil valves (if desired) in response to a call for heat from a low voltage control circuit|
Intermittent ignition is on while the burner is on|
Solid state flame sensing circuit|
External button to manually reset safety switch after lockout|
Enclosed safety switch must be manually reset after safety shutdown|
R8184M includes 4 VA transformer and Y and G terminals for connection of cooling equipment|
Mounts on standard 4 x 4 in junction box|
C554A cadmium sulfide flame detector and 24 VAC thermostat required|
22.2 to 44.4 A at 12 to 24 VAC for locked rotor
Honeywell Protectorelay Oil Burner Control, 120/240 VAC, 3.7 to 7.4 A, Intermittent Ignition, -40 to 130 deg F, Junction Box Mount, 4-3/8 in H x 4 1/8 in W x 2 1/2 in D, Domestic