Maxitrol® Line Regulator, Lever Acting Design, Series: 325, 1-1/4 in Nominal Size, Thread, 2 psi, -40 to 205 deg F, 8 in Inlet to Outlet Length, Aluminum Body, 7.3 in H.
Suitable for multi-positional mounting, If ball check vent limiting device is installed, mount in an upright position onlyNote: capacities are used to determine the maximum multiple appliance load, the largest single appliance served by the regulator should not exceed the maximum individual load specified aboveMinimum Regulation: Suitable for pilot flow applications65 psi emergency exposure limit (inlet side only)1/2 in NPT vent connection6.1 in swing radiusMaximum Individual Load: 1250000 Btu/hrTotal load of multiple appliance combined capacity: 1250000 Btu/hr7 to 11 in wc, 1.7 to 2.7 kPa at 2 psi (white CSA certified springs)
Suitable for multi-positional mounting, If ball check vent limiting device is installed, mount in an upright position only
Note: capacities are used to determine the maximum multiple appliance load, the largest single appliance served by the regulator should not exceed the maximum individual load specified above
Minimum Regulation: Suitable for pilot flow applications
65 psi emergency exposure limit (inlet side only)
1/2 in NPT vent connection
6.1 in swing radius
Maximum Individual Load: 1250000 Btu/hr
Total load of multiple appliance combined capacity: 1250000 Btu/hr
7 to 11 in wc, 1.7 to 2.7 kPa at 2 psi (white CSA certified springs)